Electric wire & Cable

PRODUCT

Flame Retardant Cable

60502-1

0.6/1kV Flame Retardant Crosslinked Polyethlene Insulated Power Cable

It uses for power circuits at less than 0.6/1kV. It is excellent in electrical, physical and chemical characteristics. It is superb in plenum feature, compared to PVC sheath cable.

  • Conductor
  • Interlock copper wire for electricity(Circle, Stranded Compacted Circle)
  • Insulator
  • XLPE
  • Union
  • Combining insulated cores as a round shape when it is more than 2 core
  • Sheath
  • PVC/ST2
  • Insulator Color
  • 2 Core - Black, White
    3 Core - Black, White, Red
    4 Core - Black, White, Red, Green
No. Cores Conductor Thickness of Insulator Thickness of Sheath Overall Diameter (Approx.) Conductior Resistance Test Voltage Weight Calculation
Nominal Cross Sectional Area Diameter of Wire Diameter (Approx.)
C Ω/㎞ v/5min ㎏/㎞
1 1.5 1/0.53 1.59 0.7 1.4 6.3 12.1 3500 60
2.5 7/0.67 2.01 6.7 7.41 75
4 7/0.85 2.55 7.2 4.61 95
6 7/1.04 3.12 7.8 3.08 115
10 7/1.35 4.05 9.4 1.83 160
16 C.C 4.70 10 1.15 220
2 1.5 1/0.53 1.59 0.7 1.8 11 12.1 3500 130
2.5 7/0.67 2.01 12 7.41 160
4 7/0.85 2.55 13 4.61 210
6 7/1.04 3.12 14 3.08 260
10 7/1.35 4.05 17 1.83 365
16 C.C 4.70 18.5 1.15 490
3 1.5 1/0.53 1.59 0.7 1.8 11.5 12.1 3500 155
2.5 7/0.67 2.01 12.5 7.41 190
4 7/0.85 2.55 13.5 4.61 255
6 7/1.04 3.12 14.5 3.08 330
10 7/1.35 4.05 18 1.83 470
16 C.C 4.70 19.5 1.15 650
4 1.5 1/0.53 1.59 0.7 1.8 12.5 12.1 3500 180
2.5 7/0.67 2.01 13.5 7.41 235
4 7/0.85 2.55 14.5 4.61 305
6 7/1.04 3.12 16 3.08 405
10 7/1.35 4.05 20 1.83 590
16 C.C 4.70 22 1.15 820