Insulated Electric Wire
60227 KS IEC 02
450/750V PVC Insulated Flexible Wire
It is used mainly for the fixed wiring of electric equipment up to and including AC 450/750V
Conductor | Thickness of Insulator | Overall Diameter (Approx.) | Conductior Resistance | Insulation Resistance | ||||
---|---|---|---|---|---|---|---|---|
Nominal Cross Sectional Area | Maximum Diameter of Wire | Diameter (Approx.) | Min. Low | Max. Low | Copper | Tin-Coated Copper | ||
㎟ | ㎟ | ㎟ | ㎟ | ㎟ | ㎟ | Ω/㎞ | Ω/㎞ | ㏁/㎞ |
1.5 | 0.26 | 1.6 | 0.7 | 2.8 | 3.4 | 13.3 | 13.7 | 0.010 |
2.5 | 0.26 | 2.1 | 0.8 | 3.4 | 4.1 | 7.98 | 8.21 | 0.009 |
4 | 0.31 | 2.6 | 0.8 | 3.9 | 4.8 | 4.95 | 5.09 | 0.007 |
6 | 0.31 | 3.6 | 0.8 | 4.4 | 5.3 | 3.30 | 3.39 | 0.006 |
10 | 0.41 | 4.8 | 1.0 | 5.7 | 6.8 | 1.91 | 1.95 | 0.0056 |
16 | 0.41 | 6.0 | 1.0 | 6.7 | 8.1 | 1.21 | 1.24 | 0.0046 |
25 | 0.41 | 7.4 | 1.2 | 8.4 | 10.2 | 0.780 | 0.795 | 0.0044 |
35 | 0.41 | 8.7 | 1.2 | 9.7 | 11.7 | 0.554 | 0.565 | 0.0038 |
50 | 0.41 | 10.4 | 1.4 | 11.5 | 13.9 | 0.386 | 0.393 | 0.0037 |
70 | 0.51 | 12.5 | 1.4 | 13.2 | 16.0 | 0.272 | 0.277 | 0.0032 |
95 | 0.51 | 14.5 | 1.6 | 15.1 | 18.2 | 0.206 | 0.210 | 0.0032 |
120 | 0.51 | 16.2 | 1.6 | 16.7 | 20.2 | 0.161 | 0.164 | 0.0029 |
150 | 0.51 | 18.2 | 1.8 | 18.6 | 22.5 | 0.129 | 0.132 | 0.0029 |
185 | 0.51 | 20.2 | 2.0 | 20.6 | 24.9 | 0.106 | 0.108 | 0.0029 |
240 | 0.51 | 23.3 | 2.2 | 23.5 | 28.4 | 0.0801 | 0.0817 | 0.0028 |